Features:
3 channels of 14 bits precision current input, 4 channels of PT100 temperature input and 2 channels 10 bits precision voltage output
3 channels of current,0~20mA and 4~20mA are optional; 2 channels of voltage, 0~5V and 0~10V are optional. They can be set by host machine.
Platinum resistance input, PT100
3 channels A/D and 4 channels PT input with PID adjust function.
Can be set as special function module for XC series PLC, up to 7 modules can be connected.
General specifications
|
Item |
Analog current input(AD) |
Temperature input (PT) |
Analog voltage output(DA) |
|
Analog input |
DC0~20mA,4~20mA |
PT100 |
- |
|
Range of temperature detect |
- |
-100~350°C |
- |
|
Max output range |
DC0~40mA |
- |
- |
|
Range of analog output |
- |
- |
DC0~5V,0~10V (External load resistance 2KΩ~1MΩ) |
|
Range of digital input |
- |
- |
10 bits(0~1023) |
|
Range of digital output |
14 bits(0~16383) |
-1000~3500 |
- |
|
Resolution |
1/16383(14Bit); Converted data are stored in PLC(14Bit) in hex form |
0.1°C |
1/1023(10Bit); Converted data are stored in PLC in hex form(10Bit) |
|
PID output value |
0~K4095 |
- |
|
|
Integrated accuracy |
0.8% |
±0.5°C |
0.8% |
|
Convert speed |
20ms/1 channel |
3ms/1 channel |
|
|
Power for analog |
DC24V±10%,100mA |
||
|
Installation |
Fixed with M3 strews or directly installed in DIN46277(35mm width) guide rail |
||
|
External dimension |
63mm×102mm×73.3mm |
||