If you need more than 10pcs and want to get better wholesale price, please feel free to contact us by following:
email:service@fasttobuy.com
Tel:0086-755- 82546545
We will quote you our best price to you in 24hours.

Features:
8 DI/6 DO, AC220 or DC24V power supply
Support power-off retentive
Support basic logic control and data operation
Support high speed count, pulse output, external interruption, C language function block, free switch for I/O points, free protocol communication and MODBUS communication.
Can not support expansion module and BD board.
Specifications:
General
|
Item |
Specification |
|
Insulation Voltage |
Above DC 500V 2MΩ |
|
Noise Resistance |
1000V 1uS pulse for 1 minute |
|
Environment Temperature |
0 °C ~60 °C |
|
Ambient Humidity |
5%~95% |
|
COM 1 |
RS-232, be connected to host machine or HMI for programming or debugging |
|
COM 2 |
RS-485/RS-232, network or connect to intelligent instrument, inverter, etc. |
|
Installation |
M3 screw fixed or DIN46277 (35mm width) guide rail installation |
|
Grounding |
The third type grounding (Never perform common grounding with strong power system) |
Performance:
|
Item |
Specification |
|
|
Program Operation Mode |
Circulation scanning mode, timing scanning mode |
|
|
Program Mode |
Instructions and ladder chart |
|
|
Dispose Speed |
0.5us |
|
|
Power Failure Holding |
FlashROM |
|
|
User Program’s Capacity |
128K |
|
|
I/O Points |
8 input points, 6 output points |
|
|
Output Format |
Relay |
|
|
Power Supply |
AC220V/DC24V |
|
|
Interior Coil’s Points (M) |
8512 points |
|
|
Timer(T) |
Points |
640 points |
|
Specification |
100mS timer: set time 0.1~3276.7 seconds 10mS timer: set time 0.01~327.67 seconds 1mS timer: set time 0.001~32.767 seconds |
|
|
Counter(C) |
Points |
640 Points |
|
Specification |
16 bits counter: Set value K0~32767 32 bits counter: Set value K0~2147483647 |
|
|
Data Register(D) |
2512 characters |
|
|
FlashROM Register(FD) |
768 characters |
|
|
High-speed Count Format |
High speed counter, pulse output, exterior interruption |
|
|
Timing Scanning Interval Setting |
0~99mS |
|
|
Password Protection |
6 characters ASCII |
|
|
Self-diagnose Function |
Power on self-diagnose, monitor timer, grammar check |
|

Xinje OP,HMI,Stepper Drive. PLC are widely used on food processing machine, automatic hydraulic machine, packaging machine, sleeve labeling machine, bag making machine, temperature control system, central air conditioning, production control and other industries.
Tell us what you think about this item, share your opinion with other people. Please make sure that your review focus on this item. All the reviews are moderated and will be reviewed within two business days. Inappropriate reviews will not be posted.
Have any question or inquire for this item? Please contact us. Our customer representative will get back shortly.