1. DVP06XA-S is able to receive 4 points of analog input signals (voltage or current) and convert them into 12-bit digital signals. DVP06XA-S receives 2 groups of
12-bit digital data from the PLC MPU and converts them into 2 points of analog signals for output (in voltage/current). There are 49 16-bit control registers (CR) in DVP06XA-S, and the data in it can be read and written by using FROM/TO instructions in DVP Slim series PLC MPU program.
2. The system version of DVP06XA-S can be updated via RS-485 communication. The power unit is separate from it and is small in size and easy to install.
3. The user can select voltage or current input by wiring. Range of voltage input: +-10VDC (resolution: 5mV). Range of current input: +-20mA (resolution: 20uA).
4. The user can also select voltage or current output by wiring. Range of voltage output: 0V ~ +10VDC (resolution: 2.5mV). Range of current output: 0mA ~ 20mA (resolution: 5uA).
Specifications:
Mixed analog/digital (A/D) module |
Voltage input |
Current input |
Power supply voltage |
24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%) |
|
Analog input channel |
4 channels per module |
|
Analog input range |
+-10V |
+-20mA |
Digital data range |
+-2,000 |
+-1,000 |
Resolution |
12 bits (1LSB=5mV) |
11 bits (1LSB=20uA) |
Input impedance |
200K? and above |
250? |
Overall accuracy |
+-0.5% of full scale of 25°C (77°F). +-1% of full scale during 0 ~ 55°C (32 ~ 131°F). |
|
Response time |
3ms × channels |
|
Isolation method |
There is no isolation between channels |
|
Absolution input range |
+-15V |
+-32mA |
Digital data format |
2’s complement of 16-bit, (13 significant bits) |
|
Average function |
Yes (CR#2 ~ CR#5 can be set and the range is K1 ~ K4,095) |
|
Self diagnostic function self detection |
Upper bound and lower bound detection per channel |
|
Mixed digital/analog (D/A) module |
Voltage output |
Current output |
Analog signal output channels |
2 channel per module |
|
Analog output range |
0 ~ 10V |
0 ~ 20mA |
Digital data range |
0 ~ 4,000 |
0 ~ 4,000 |
Resolution |
12 bits (1LSB=2.5mV) |
12 bits (1LSB=5uA) |
Output impedance |
0.5? or lower |
|
Overall accuracy |
+-0.5% of full scale of 25°C (77°F). +-1% of full scale during 0 ~ 55°C (32 ~ 131°F) |
|
Response time |
3ms × channels |
|
Max. output current |
20mA (1K? ~ 2M?) |
/ |
Tolerance carried impedance |
/ |
0 ~ 500? |
Digital data format |
2’s complement of 16-bit, (13 significant bits). |
|
Isolation method |
Isolation between digital and analog circuitry. There is no isolation between channels. |
|
Protection |
Voltage output has short circuit protection but long period of short circuit may cause internal wiring damage and current output break. |
|
Communication mode (RS-485) |
MODBUS ASCII/RTU Mode. Communication baud rate of 4,800/9,600/19,200/38,400/57,600/115,200. For ASCII mode, date format is 7 bits, even, 1 stop bit (7, E, 1). For RTU mode, date format is 8 bits, even, 1 stop bit (8, E, 1). The RS-485 is disabled when the DVP06XA-S is connected in series with MPU. |
|
Connect to DVP-PLC MPU in series |
When DVP06XA-S modules are connected to an MPU, the modules are numbered from 0-7. 0 is the closest to the MPU and 7 is the furthest. The Maximum number of modules is 8 modules and they do not occupy any digital I/O points of the MPU. |
|
Power supply |
||
Maximum power consumption |
2W at 24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%), supplied by external power |
|
Environment |
||
Operation/storage |
Operation: 0°C ~ 55°C (temperature); 50 ~ 95% (humidity); pollution degree 2. Storage: -25°C ~70°C (temperature); 5 ~ 95% (humidity). |
|
Vibration/shock immunity |
International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 (TEST Ea) |
Product Profile & Dimension
Shipment:
1. Usually we will ship the items within 3 working days after the payment is reached.
2. DHL, UPS, Fedex, or EMS is available for shipping.
4. Delivery time:
DHL, UPS, Fedex, EMS express shipping usually take 3-10 working days depends on the country delivered to.
4. Please check out your ADDRESS carefully when processing order.
5. Buyers please note: Accessories tariffs must be buyers to pay.The buyer can choose EMS express to avoid tariffs.
6. Any accidents, delays or other issues are the responsibility of the shipping service.
We promise to:
Provide 24/7 customer support.
Offer our customers the low Chinese price.
Streamline the buying and paying process.
Deliver goods to our customers all over the world with speed and precision.
Ensure the excellent quality of our products.
Help you find products and manufacturers in China.
Return Policy:
We accept 14 days return policy. If you want to return the item, please contact us in 14 days first and make sure the package is un-opened. The buyer has to pay for the go and back delivery cost and the custom fee of each country. Once we received the product and checked, we will make refund for the part in 24 hours.
Any quality problem in normal use during the warranty period, we will repair for free. The buyer should pay the return cost and our company will pay the re-shipping cost.
Tell us what you think about this item, share your opinion with other people. Please make sure that your review focus on this item. All the reviews are moderated and will be reviewed within two business days. Inappropriate reviews will not be posted.
Have any question or inquire for this item? Please contact us. Our customer representative will get back shortly.