DVPPS05 Delta PLC 85-264VAC DC24V 5A output current 1-Phase Power Supply Original brand new

DVPPS05 Delta PLC 85-264VAC DC24V 5A output current 1-Phase Power Supply Original brand new

 

Introduction


DVPPS series is a power module with 3 types that sorted by output circuit. 1. DVPPS01 provides 24V DC and 1A current for output power. 2. DVPPS02 provides 24V DC and 2A current for output power. 3. DVPPS05 provides 24 V DC and 5 A current for output power. DVPPS series is only used for Delta DVP series. DVPPS series is separated from the PLC MPU for better space utilization and easier installation.

Electrical Specifications

Model

Item

DVPPS01

DVPPS01

DVPPS01

Power input

100 ~ 240VAC (-15% ~ +10%), 50/60Hz

Output power

24VDC (±3%)

Maximum output current

1A

2A

5A

Ripple & noise

Under 100mVp-p Typical at

full load

Under 240mVp-p Typical at full load

Efficiency

78% ~ 87% Typical at full load

Above 88% Typical at full load

Overcurrent/short circuit protection

Auto Recovery

Overvoltage/

overtemperature

protection

 

Overvoltage protection: The

power supply is cut off for 5 seconds. DVPPS05 operates

normally after power is supplied.

Over temperature protection:

The power supply is cut off for

5 seconds, and the

Temperature inside DVPPS05 falls to the temperature below 85oC. DVPPS05 operates Normally after power is supplied.

Grounding

The diameter of grounding wire cannot be smaller than the wire diameter of terminals L and

N (All PLC units should be grounded directly to the ground pole).

Operation environment

0°C~55°C (temperature), 50~95% (humidity), Pollution

degree 2

-20°C~55°C (temperature),

50~95% (humidity),

Pollution degree 2

Storage environment

-25°C~70°C (temperature), 5~95% (humidity)

Agency

approvals

UL

UL508 Listed (Industrial Control Equipment)

CE

European Community EMC Directive 89/336/EEC and Low Voltage Directive

73/23/EEC

EMC Directive 2004/108/EC and Low Voltage Directive

2006/95/EC

Weight (g)

158

250

488

           

Product Profile

DVPPS01-DVPPS02-DVPPS05-product-profile.jpg 

Tell us what you think about this item, share your opinion with other people. Please make sure that your review focus on this item. All the reviews are moderated and will be reviewed within two business days. Inappropriate reviews will not be posted.

Have any question or inquire for this item? Please contact us. Our customer representative will get back shortly.

Related Categories